A Word on Managing Calibrations



I’ll often hear my customers say something along the lines of “I really wish we could get a more accurate consistency transmitter”.  When I dig a little deeper, I usually find that the problem isn’t necessarily so much an issue with the transmitter’s accuracy, but rather, with the way that the calibration for that transmitter is built and managed.

What do I mean?

When somebody installs a consistency transmitter, what they usually want is for that transmitter to generate a consistency number that agrees with whatever their lab says.  If the lab analyzes a stock sample and says its 3.4%, they want the transmitter to say 3.4%, too.

Of course, the reality is that the transmitter will never actually read 3.4%. It will always be different.  Always.

What most people don’t fully understand is that this behavior is absolutely normal.  The question isn’t if the transmitter and the lab disagree, because they will.  The real question is how much can the lab and transmitter disagree before you start to think that you’ve really got a problem.

And that’s a question that far too few people ask.  The consequences of not asking that question can be severe.  Take this scenario, for example.

The operators get a consistency reading, X, from the lab.  The value of X doesn’t agree with what the transmitter is saying, which is reading Y.  The operators call the E&I shop and tell them that they need to go and service the transmitter so that it reads X instead of Y. 

In a couple of hours, or maybe the next day, an E&I tech goes to the transmitter in question and adjusts the output so that it now reads X.  When the operators get the next lab analysis, they note that while the transmitter is now reading X, the lab now says it's actually Z.  So, again, they call up the E&I shop and tell them that transmitter has drifted again, and now they need to make it read Z instead of X. 

The E&I shop dutifully dispatches another tech, probably not the same one as before, who goes to the transmitter and readjusts it to now read Z.  It’s a good bet, by the way, that the first and second tech don’t use the same method to adjust the transmitter.  The next lab sample evaluation comes, and now, it’s W, instead of X, Y, or Z.  By this time, everybody starts calling the transmitter “that damn transmitter” and walks around cussing out the vendor for his piece of s**t instrument.

Does that sound familiar?

This is a situation that can be avoided if one knows the statistics behind a calibration.  When you build a calibration, there is something that you have accept as if it were the Gospel truth:  the instrument is better than your lab. 

What I mean by that is that your instrument will likely respond pretty much the same way given the same process conditions with very little variation.  Most undamaged and properly functioning instrumentation will respond with less than 1% of variation.

The same can’t be said of the lab.

This doesn’t mean that your lab is bad, or that your lab techs are lazy slobs.  It’s just the nature of the beast when it comes to manual analyses.

The TAPPI T-240 method for establishing consistency, for example, reports a repeatability standard of only 10%, and that presumes that your sampling techniques isn’t adding a whole lot more error.

In real terms, that means that you would expect that if the first lab analysis said 3.0%, then 95% of the time, you would expect a second analysis of the same stock to not deviate by more than 0.3%, or in other words, to come in somewhere between 2.7% and 3.3%.

That’s a pretty big range.  And you get that if you’re doing it properly. 

Now, what does this mean, exactly?

It doesn’t mean that your consistency readings are worthless.  Quite the contrary, it means that you now have a benchmark by which you can gauge the health of your consistency readings.

Remember that the instrument is probably responding to real changes in consistency with a repeatability variability of less than 1%.  If your calibration was built properly in the first place – a topic for another column, by the way – then if the lab typically reports X when the meter is reading Y, you shouldn’t get excited until the lab value exceeds X +/- 10% of X.

Remember, 95% of the time, you expect that lab to get within that 10% of X.  If it is within that 10%, then, everything is working OK and you shouldn’t mess with your transmitter or the calibration.

I wouldn’t even get excited if you occasionally get a reading in excess of 10% of X.  Remember, 95% of the time you expect it to be less, but that also means that 5% of the time, or about once every twenty times, it could be more than 10% and everything would still be OK.

So when should you get excited?

If your readings are consistently deviating more than that 10% of X, then it’s time to review the situation.

If your variation is always positive, or always negative, then it’s time to review the situation.  A valid calibration should see both positive and negative variation.

I stop here for now, but I’ll leave you with one more thought.  You can do a lot better than that 10%.  More on that in a future column.

Epiphany


E-piph-a-ny - [ih-pif-uh-nee] - a sudden,intuitive perceptionof or insight intothe reality or essential meaning of something, usuallyinitiated by some simple, homely, or commonplace occurrenceor experience.

I had an epiphany the other day, which is rather rare for me.  I was thinking about paper machines when it hit me…

A paper machine is nothing more than a giant water removal device.  I mean, wet stuff goes in one end and dry stuff comes out the other end.   Sure, there’s a lot more to it than that, but when you boil it down to its simplest, most fundamental function, that’s what a paper machine does – it removes water from paper stock.  And if that’s true, then how water drains from paper stock is probably the most fundamental aspect of the paper making process, right?  Any change to the drainage quality of your stock will impact the function of the paper machine.

You’ll see it in how the wet line moves.

You’ll see it in the couch vac.

You’ll see it in the press section.

You’ll see it in the dryers.  And so on…

If the drainage quality of the stock will impact the fundamental function of the paper machine, then controlling the drainage quality of the stock is probably the most fundamental aspect of the paper making process.  And before you can control it, you have to measure it.

Gee, I wonder how you can do that?